SPECIFICATION - OXYGEN TWO WIRE
4-20 mA TRANSMITTER
UNIPHOS –
510T
Gas
:
Oxygen (O2)
Resolution
(ppm)
:
0.1 %
Detection
Principle
:
Sealed Electrochemical Sensor
Gas
Sampling
:
Diffusion
Accuracy
:
Inherently ± 2% (But
also depends on
accuracy of calibration
gas)
Operating
Life of Sensor
:
Expected life 1 – 2 year.
Warranted for one year.
Operating
Temperature
:
0 to 40 °C
Operating
Pressure
:
Ambient ±
10%
Power
Supply from
Controller
/ DCS
:
15 – 24 V DC
Height =
70 mm